Electrical Wire Size Calculator by Distance

To size electrical wire over distance, calculate voltage drop using conductor circular mils and one-way footage. If voltage loss exceeds 3% under continuous load (NEC 210.19(A)), upsize the conductor to the next standard AWG gauge and increase the equipment ground wire proportionately per NEC 250.122(B).

LONG DISTANCE WIRE SIZING SCHEMATIC
#8 AWG Cu • 2.08% Drop
DETAIL A: WIRE UPSIZING ZOOM (3.5X) BASE CODE GAUGE #12 AWG Cu 5.27% Drop UPSIZED FOR DISTANCE #8 AWG Cu 2.08% Drop (OK) • NEC 210.19(A): Upsized to limit drop to ≤3%. • NEC 250.122(B): Ground upsized to #8 AWG Cu. BREAKER PANEL 20A 120V SOURCE Load: 16A #8 AWG Cu EGC: #8 AWG Cu 100 FEET REMOTE LOAD 117.5V AT TERMINAL -2.5V (2.08%) LINE VOLTAGE LOSS VOLTAGE DROP FORMULA: V_drop = (2 × K × I × L) / C_M Base: #12 AWG Cu (5.27% drop) → Recommended: #8 AWG Cu (2.08%) 0% (PERFECT) 3.0% (NEC TARGET) 5.0% (MAX BRANCH) Conductor upsized by 2 gauge sizes to maintain <=3% voltage drop. CIRCUIT: 20A @ 120V | DISTANCE: 100 FT | LOAD VOLTAGE: 117.5V
✦ NEC 210.19(A): #8 AWG Cu for 100' Run
Drop: 2.08% (2.5V) Terminal Voltage: 117.5V
Circuit Parameters 3% Drop Standard
20 Amps (16A Continuous)
100 Feet
10 ft 100 ft (Drop Threshold) 400 ft (Extreme Run)
Contractor Wire Sizing Takeoff Upsized +2 Steps
RECOMMENDED WIRE GAUGE
#8 AWG Cu
EQUIPMENT GROUND (EGC)
#8 AWG Cu
ACTUAL VOLTAGE DROP
2.5V (2.08%)
VOLTAGE AT LOAD END
117.5V
Base vs. Upsized Gauge
Base Code: #12 AWG Cu (5.27% drop) → Recommended: #8 AWG Cu (2.08% drop)

Long-Distance Conductor Sizing: Wire Gauge Distance Calculator & Engineering Principles

In electrical construction, this electrical wire size calculator and wire gauge distance calculator sizes conductors across long runs. While NEC Table 310.16 establishes thermal ampacity limits, thermal ratings only ensure insulation survives without overheating over short distances.

When feeding outbuildings or machinery, our voltage drop wire size calculator and electrical cable distance calculator serves as an authoritative long run wire gauge sizer. Beyond 100 feet, internal resistance drops terminal voltage, overheating motors and tripping sensitive electronics.

THHN Wire Size Distance Chart & Conductor Resistances

Reference this thhn wire size distance chart and contractor wire sizing chart by distance to compare conductor area in circular mils wire gauge against standard wire resistance ohm per 1000 ft for uncoated solid and stranded copper:

Conductor Size Circular Mil Area (C_M) 75°C Cu Ampacity Resistance (Ω/1,000 ft Cu) Typical Max Circuit Length (3% Drop)
#14 AWG 4,110 15A (NEC 240.4) 3.07 Ω 50 Feet (at 12A continuous)
#12 AWG 6,530 20A (NEC 240.4) 1.93 Ω 60 Feet (at 16A continuous)
#10 AWG 10,380 30A (NEC 240.4) 1.21 Ω 80 Feet (at 24A continuous)
#8 AWG 16,510 50A 0.764 Ω 115 Feet (at 32A continuous)
#6 AWG 26,240 65A 0.491 Ω 150 Feet (at 40A continuous)
#4 AWG 41,740 85A 0.308 Ω 200 Feet (at 50A continuous)

The Single-Phase Voltage Drop Formula & NEC 210.19 Standards

Under nec 210 19 voltage drop guidelines, electricians evaluate total line loss across two current-carrying conductors to keep branch circuit voltage drop 3 percent or lower:

V_drop = (2 × K × I × L) / C_M

Where K is conductor resistivity (12.9 ohms-cmil/ft for copper; 21.2 for aluminum), I is circuit load current in amperes (evaluated at 80% continuous rating), L is one-way circuit length in feet, and C_M is circular mil area. Whenever line loss exceeds 3%, you must upsize wire for distance to guarantee equipment safety and system efficiency.

Sizing 120V and 240V Circuits: Outdoor Sheds, EV Chargers & Subpanels

Voltage choice dictates distance limits. In a 120v wire size by distance run or a 240v wire size calculator analysis, doubling voltage cuts current in half for identical wattage, reducing line drop by 75%. In copper vs aluminum wire distance evaluations, aluminum requires roughly 1.6 times copper circular mil area for equivalent resistance.

Field applications include sizing as an outdoor shed wire size calculator, finding ev charger wire gauge distance for Level 2 EVSE chargers, and calculating subpanel wire size distance for detached garages.

The Critical Inspector Catch: NEC 250.122(B) Equipment Ground Upsizing

Under nec 250 122 b ground upsizing rules, ungrounded conductors upsized for voltage drop require equipment grounding conductors (EGC) to scale proportionately:

"Where ungrounded conductors are increased in size from the minimum size that has sufficient ampacity for the intended installation, wire-type equipment grounding conductors, where installed, shall be increased in size proportionately according to the circular mil area of the ungrounded conductors."

If a 20A circuit at 120 feet is upsized from #12 AWG (6,530 CM) to #8 AWG (16,510 CM), the grounding conductor must also be upsized to #8 AWG to preserve rapid breaker tripping under ground fault conditions.

Electrical Wire Sizing by Distance Frequently Asked Questions

What is the required 20 amp wire size 100 feet from the panel? ▼

For a 20 amp wire size 100 feet run on a 120V branch circuit at 16A continuous draw, standard #12 AWG copper produces a 4.1% voltage drop (4.9V drop). To satisfy the 3% NEC limit, upsize to #10 AWG copper, which drops 2.6% (3.1V), and upsize the ground to #10 AWG.

What is the recommended 50 amp wire size 150 feet out? ▼

For a 50 amp wire size 150 feet run on a 240V split-phase feeder drawing 40A continuous load, standard #6 AWG copper drops 3.1% (7.4V drop). Upsizing to #4 AWG copper drops only 1.9% (4.6V) and maintains full voltage stability.

Do I have to upsize the ground wire when I upsize the hot wire? ▼

Yes. Under NEC Article 250.122(B), whenever you upsize circuit conductors for voltage drop or length, you must scale the equipment grounding conductor by the same circular mil ratio to preserve safe clearing time during a fault.

What is the maximum acceptable voltage drop under NEC? ▼

NEC Informational Note 210.19(A) recommends keeping branch circuit voltage drop under 3% at maximum continuous load, with total combined feeder plus branch circuit drop under 5% from service entrance to final outlet.